Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Electric Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Altitude:≤2000mm;
Ambient air temperature:-40C-+45ºC;
Wind speed: 34m/s;
Earthquake intensity:8degree;
Relative humidity: monthly average 90%, daily average 95%;
Ice thickNess: 10mm;
Pollution degree: IV;
There will be have dew under the condition of high temperature low down hastily.
Name | Unit | Data | |||
16kA | 20kA | 25kA | |||
Rated voltage | kV | 10 | |||
Max. operation voltage | kV | 12 | |||
Rated current | A | 630/1250 | |||
Rated short-circuit breaking current | kA | 16 | 20 | 25 | |
Rated short-circuit making current | kA | 40 | 50 | 63 | |
Rated peak withstand current | kA | 40 | 50 | 63 | |
Rated short-time withstand current | kA | 16 | 20 | 25 | |
Rated Insulate level | 1min P.F withstand voltage | kV | 42/48 | ||
Lightning impulse withstand voltage(peak) | kV | 75 | |||
Rated operating sequence | O-0.3s-CO-180s-CO | ||||
Mechanical life | times | 10000 | |||
Rated short-circuit breaking current breaking times | times | 30 | |||
Rated Operating Setup Closing Voltage | V | AC220 DC220,100 | |||
Rated Operating Setup Opening Voltage | V | AC220 DC220,100 | |||
Contact Stroke | mm | 11±1 | |||
Contact Over travel (Contact Spring Constringent Length) | mm | 3 | |||
Out Of Simultaneity Of Contact Closing And Opening | ms | ≤2 | |||
Contact Closing Bounce Time | ms | ≤2 | |||
Average opening Speed | m/s | 1.0±0.2 | |||
Average Closing Speed | m/s | 0.7±0.15 | |||
Opening Time | The Highest Operating Voltage | s | 0.015-0.05 | ||
The Lowest Operating Voltage | s | 0.03-0.06 | |||
Contact Closing Time | s | 0.025-0.05 | |||
Current by Phase Circuit Resistance | μΩ | ≤120(≤200) | |||
Contact erosion limit | mm | 3 |