Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Electric Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Outdoor high-voltage AC single pole isolation switches (hereinafter referred to as "isolation switch") are outdoor high-voltage power distribution equipment with a rated voltage of 24kV and three-phase AC 50Hz, which are applicable to 20kV high-voltage transmission lines to cut off and close single-phase or three-phase circuits without load and voltage.The rated current of the isolation switch is 200A, 400A, 600A, and 1000A.
The altitude does not exceed 3000m.
The ambient air temperature: Maximum:+40ºC; Minimum:-30ºC, Paramos:-40ºC
The wind pressure does not exceed 700Pa. (corresponding to 34m/s wind speed).
Atmospheric relative humidity: Dailly average does not exceed 95%, Monthly average does not exceed 90%
The installation site of an ordinary type isolator should be kept away from gas, smoke chemical deposition,salt-spray fog, dust, and other explosive and corrosive matters that affect seriously the insulation and conduction capability of the isolator.
Pollution-proof type isolator is applied to severe filthy conduction areas; however, it shouldn't be any explosive matters and matters causing a fire.
The contacts adopt L-shaped contacts, with a guide set at the top to ensure that the moving contacts are closed at the correct position
Set up a locking device to ensure strong closing stability; the locking device is made of S304 stainless steel, which can effectively solve corrosion; it can be unlocked at any installation angle during operation, and the horizontal transverse locking device is the first application in the industry.
The main conductor is made of T2Y copper profile, which has strong flow capacity; the moving contact (contact plate) is made of flanged profile, which has high strength; the static contact is made of R-shaped structural profile, which is flexible in opening and closing and has reliable line.
The contact surface adopts advanced silver plating technology and has a type test report issued by a third party. Non-conductive surface tinned.
Name | Unit | Data | |
Rated voltage | kV | 24 | |
Rated current | A | 630/1250 | |
Disconnector | Rated peak withstand current | kA | 63 |
Rated short-time withstand current | kA | 25 | |
Rated duration of short-circuit | s | 4 | |
Rated short time power frequency withstand voltage(RMS) | To earth | kV | 95 |
Open contact | 118 | ||
Rated lightning impulse withstand voltage(peak) | To earth | kV | 185 |
Open contact | 215 | ||
Rated terminal static mechanical load | Horizontal longitudinal | N | 1000 |
Horizontal crosswise | 750 | ||
Vertical force | 1000 | ||
Mechanical endurance | times | 3000 |