Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Electric Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Outdoor high voltage isolate switch is a single-phase AC frequency 50 Hz / 60HZ high voltage switch equipment .The product is suitable for power system with rated voltage 10kV to 23KV. It can connect or break the power system under the circumstances of with voltage or non-load.The switch is operated by using insulating rod.
Altitude: no more than 1000m. If the altitude is higher than 1000m, the rated insulation level shall be corrected accordingly.
Ambient temperature: upper limit + 45 0C, lower limit - 40 0C, average temperature of the hottest month 30 0C, maximum daily temperature difference 25K.
Solar radiation intensity (outdoor): 0.1W/cm2
Wind speed / pressure (outdoor): 34m/s / 700Pa
Pollution level: e-level
Icing thickness: not more than 20mm
Humidity: average daily relative humidity, not more than 95%, average monthly relative humidity not more than 80%
Earthquake resistance: horizontal acceleration 0.3m/2, vertical acceleration 0.15m/s2
Safety factor: sinusoidal resonance three cycle wave, safety factor above 1.67.
GW1-10 type outdoor AC high voltage isolation switch is composed of three identical single-pole isolation switches.
In the installation, the three poles are formed into a whole by the pipe connecting rod, and the CS8-1 manual operation mechanism is used.
Each single-pole isolation switch has a separate iron frame with two post insulators installed at both ends and contacts installed on them.
There is a rotating shaft in the middle of the iron frame, and the tool brake is closed by means of a tie rod insulator.
Name | Unit | Data | |||||
Rated voltage | kV | 10 | 15 | 20 | |||
Maximum operating voltage | kV | 12 | 7.5 | 23 | |||
Rated insulation level | 1 min power frequency withstand voltage | To earth | kV | 40 | 40 | 50 | |
Open contact | kV | 47 | 47 | 60 | |||
Lightning shock withstand voltage(peak) | To earth | kV | 105 | 105 | 125 | ||
Open contact | kV | 120 | 120 | 145 | |||
Rated frequency | Hz | 50 | |||||
Rated current | A | 200 | 400 630 | 1250 | |||
4S thermal stable current(effective value) | kA | 6.3 | 12.5 20 | 31.5 | |||
Dynamically-stable current(peak) | kA | 16 | 31.5 50 | 80 |