SF6 type outdoor high voltage hexafluoride circuit breaker (hereinafter referred to as "II III type circuit breaker") is a new type of outdoor high voltage electrical appliance with SF6 gas as an arc extinguishing and insulating medium. The arc extinguishing chamber adopts the principle of spin arc extinguishing, and the operating mechanism is divided into manual energy storage operating mechanism (type I). (Type II) energy storage spring operating mechanism, (type III) DC electromagnetic operating mechanism three, all kinds of operating mechanism and circuit breaker body perfect combination into a whole.
Ambient temperature: upper limit +40 degrees, lower limit -40 degrees
The altitude does not exceed 1000m
Wind pressure no more than 700Pa(wind speed no more than 35m/s)
The intensity of the earthquake does not exceed 8 degrees
There is no fire, explosion danger, serious pollution, chemical corrosion and violent vibration.
Name | Unit | Data | |||
Rated Voltage | kV | 12 | |||
Rated Insulation Level | Lightning Impulse Withstand Voltage(Full-wave Peak Value) |
kV | 75 | ||
Power Frequency Withstand Voltage(1 minute) | 42 | ||||
Rain Withstand Voltage Test | 34 | ||||
Reverse Phase impact Pressure | 85 | ||||
Insulation level under zero gauge pressure | Power Frequency Withstand Voltage(1 minute) | kV | 30 | ||
Reverse Phase Withstand Voltage(1minute) | 30 | ||||
Maximum Phase Voltage (5min) | 9 | ||||
Rated Current | 400,630 | ||||
Rated Short-Circuit Breaking Current(0.25MPa,200C time) | Times | 16,20 | |||
Outgoing phase grounding reclosing breaking current | Mpa | 14,17.4 | |||
Breaking current under zero gauge voltage | Mpa | 400,630 | |||
Rated Operating Sequence | Type I | 0-180s-C/0-180s-C/O | |||
Type II III | 0-0.3s-C/0-180s-C/O | ||||
Rated Short-Circuit Closing Current(Peak Value) | 40,50 | ||||
Rated Withstand Current (Peak Value) | 40,50 | ||||
Rated Short-time Withstand Current | 16,20 | ||||
Rated Short-Circuit Continuous Time | 4 | ||||
Rated winding charging breaking current | 25 | ||||
Rated line charging breaking current | 16 | ||||
Rigid closing speed | 2.0±0.2 | ||||
Rigid component speed | 3.6±0.2 | ||||
Opening distance of dynamic and static contacts | 37±2 | ||||
Total travel of the conductive rod | 58±2 | ||||
Conducting rod overtravel | 22±2 | ||||
Three-phase synchronism of opening and closing | ≤2 | ||||
Main circuit resistance of each phase | ≤130 | ||||
Rated Working Pressure | 0.35(200C) | ||||
Minimum Working Pressure | 0.25(200C) | ||||
Annual Gas Rate | ≤0.05 | ||||
Mechanical Stability Operation | 10000 | ||||
Water content of SF6 gas | ≤150 | ||||
Weight | 150 |