Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Electric Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Outdoor AC vacuum circuit breaker is used to make and break load current, overload current and short-circuit current in 12kV,50/60Hz power system. It's applicable for substations, industry and mining, urban and rural electricity power networks, especially applicable in occasions with frequent operation and automatic power distribution network. It accords with the standards of IEC62271-100 &GB1984 AC high voltage circuit breaker, GB/T11022 HV General technical requirement of switches and control apparatus.
1.Ambient Temperature:-40ºC~+40ºC
2.Altitude:≤2000m
3.Wind Pressure: no more than 700Pa (equal to 34m/s wind speed
4.Maximum Temperature Drop: no more than 25ºC
5. There will be have dew under the condition of high temperature low down hastily.
Name | Unit | Data |
Rated voltage | kV | 12 |
Rated power frequency | Hz | 50 |
Rated current | kA | 630/1000 |
Rated short-circuit breaking current | kA | 20/25 |
Rated withstand current(peak) | kA | 50,63 |
Rated short-time withstand current(4s) | kA | 20,25 |
Rated short-circuit making current(peak) | kA | 50,63 |
Mechanical life | times | 10000 |
Rated short-circuit breaking time | times | 30 |
Power frequency withstand voltage (1min):,white, on the ground / fracture | kV | 42/48 |
Lightning impulse withstand voltage (peak) and white, right / fracture | kV | 75/85 |
Secondary circuit 1min power frequency withstand voltage | kV | 2 |
Weight | kg | 180 |
SF6 rated gage pressure | Mpa | "0" |