Audited by an independent third-party inspection agency
The boundaries of outdoor vacuum load switch (negative dutch switch body and FDR-01-type fault detection controller) with fault detection, protection and control functions and communication functions, mounted on responsibility 10kV distribution line at the demarcation point into the line user, you can also applicable to meet the requirements of the branch line connection in conjunction with the pre-coincidence, automatic removal of single-phase ground fault isolation and automatic phase short circuit fault, and can quickly locate the point of failure.
The maximum ambient air temperature does not exceed 40ºC, not limited to not more than-45ºC;
The wind speed is not greater than 35m / s;
Altitude higher than 1000m, the earthquake intensity does not exceed 8 degrees;
Humidity: monthly average relative humidity less than 90%; daily average relative humidity less than 95%;
Ice thickNess does not exceed 10mm;
The installation site should be non-flammable, explosive, chemical corrosion and recurrent severe vibration place;
Neutral Grounding Mode: ungrounded neutral point arc suppression coil grounded neutral grounding via low resistance.
Intelligent control device, with remote intelligent operation function
Advanced solid circuit breaker technology, with high reliability and stability
With high power failure speed, low power consumption, energy saving and environmental protection
Name | Unit | Data | |||
Rated voltage | kV | 12 | |||
Rated frequency | Hz | 50 | |||
Rated current | A | 630 | |||
Active load breaking current / frequency | A/times | 630A/≥100 | |||
Rated peak withstand current | kA | 50 | |||
Rated short time withstand current | kA | 20 | |||
Rated short circuit making current (Peak) | kA | 50 | |||
Mechanical endurance | times | ≥10000 | |||
Rated duration of short circuit withstand | s | 4 | |||
Rated power frequency withstand voltage (1min) | White, relatively | Dry test, wet test | kV | 42/34 | |
Fracture | Dry test | 48 | |||
Rated lightning impulse withstand voltage | White,relatively | kV | 75/85 | ||
Fracture | |||||
Rated control voltage | V | 220 |