Outdoor AC vacuum circuit breaker is used to make and break load current, overload current and short-circuit current in12kV, 50/60Hz power system. It is applicable for substations, industry and mining, urban and rural electricity power networks, especially applicable in occasions with frequent operation and automatic power distribution network.
Altitude:≤2000mm;
Ambient temperature: -40ºC~+45C;
Earthquake intensity:8degree;
Ice thickNess:10mm;
Wind speed: 34m/s (air pressure 700Pa).
Manual brake opening device
Epoxy resin package
No maintenance, the application of bistable permanent magnet technology
The switch housing is made of stainless steel or sprayed plastic
Name | Unit | Data | ||
Rated voltage | kV | |||
Rated insulating level | 1min P.F withstand voltage-(phase to phase, to earth; across open contacts) | dry | 42/48 | |
wet | 34 | |||
Lightning impulse withstand voltage peak (phase to phase, to earth;) | 75 | |||
Lightning impulse withstand voltage peak ( across open contacts ) | 85 | |||
Rated frequency | Hz | 50 | ||
Rated current | A | 630,1250 | ||
Rated short-time withstand current | kA/4S | 20,25 | ||
Rated short-circuit breaking current | kA | 20,25 | ||
Rated short-circuit making current | 50,63 | |||
Rated peak withstand current(peak) | 50,63 | |||
Rated operating sequence | / | O-0.3s-CO-180s-CO | ||
Breaking time of rated short-circuit breaking current | times | 30 | ||
Mechanical duration | Permanent magnet mechanism 30000, spring mechanism 10000 | |||
Abrasions thickNess of contacts | mm | 3 | ||
Net weight | kt | 70 |