Customization: | Available |
---|---|
Application: | Electronic, Instrument, Position Sensor, Audio, Lighting |
Type: | Current Transformer |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
The current transformer is epoxy resin cast fully enclosed pillar structure, small size, light weight, suitable for installation in any position, any direction LZJ8-10Q current transformer is epoxy resin cast insulated fully enclosed pillar product, suitable for rated frequency 50Hz or 60Hz, rated voltage 10kV or below power system. Used for electric energy measurement, current measurement and relay protection. This product conforms to IEC60044-1 and GB1208 "Current transformer" standards.
The performance of products is conformed to IEC61869-1:2007, IEC61869-2:2012 commission requirements
Rated insulation level: 12/42/75kV
Power factor of load: COSΦ=0.8
Rated frequency: 50Hz, 60Hz
Rated secondary current: 5A or 1A
Rated insulation level: 12/42/75 kV;
Rated secondary current: 5A,1A;
Rated primary current, precise stage combination, rated output and rated dynamic and thermal stable current are shown in the table:
Pollution grade: II
Note: If the user has the requirements, the measurement level can be 0.2S, 0.5S;
Rated primary current(A) | Accuracy classes combination | Rated secondary output(VA) | 1s thermal current(kA) | Rated dynamic current(kA) | ||||
0.2S 0.5S | 0.2 | 0.5 | 10P10 | 10P15 | ||||
5-40 | 0.2(S)/10P 0.5(S)/10P |
10 | 10 | 10 | 15 | 15 | 90lin | 220lin |
50-400 | 100lin | 250lin | ||||||
500 | 50 | 100 | ||||||
600 | 56 | 110 | ||||||
800 | 75 | 110 | ||||||
1000 | 80 | 130 |